| Where the usable heat leaves | About half in the exhaust; the rest in the cooling water and the oil, below ~150 °C | Concentrated in a single hot exhaust stream |
|---|
| What the heat produces | Hot water; steam only at low pressure, below ~8.6 bar | Steam, hot water, and chilled water by absorption, without a compressor |
|---|
| Oil and filter changes | Every 250–2,000 h, depending on fuel and engine | Industrial turbine: inspection every 4,000 h · V70/V200: no lubricating oil, inspection every 8,000 h* |
|---|
| Overhauls | Top-end overhaul every 8,000–30,000 h, before the major overhaul | 2 MW module: more than 40,000 h between major overhauls · microturbines: 40,000–80,000 h |
|---|
| NOx | Catalyst in the exhaust; SCR where the limit is stricter | Below 15 ppm without treatment (industrial turbine with low-NOx burner) · V70/V200: target below 9 ppm* |
|---|
| Engine cooling | Radiator or tower for the jacket water and the oil | V70/V200: no coolant, no radiator* |
|---|
| Noise and vibration | Pistons in reciprocating motion | Continuous rotation, no pistons; V70/V200 with less noise and vibration |
|---|
| Maintenance per kWh (up to ~250 kW) | 2.2–3.0 US cents | Microturbines: 1.7–1.9 US cents |
|---|